Testing the result that Ethernet Devices B (192.168.10.101) and C (192.168.10.102) of
network 1 cannot be "pinged" by devices of network 2
Run 3 Ping commands from a device of Ethernet network 2 (192.168.20.0/24) using below described ad-
dresses (members of network 1)
 ping 192.168.10.100 (Device A)
 ping 192.168.10.101 (Device B)
 ping 192.168.10.102 (Device C)
Results:
1. Sent "Ping" to IP address 192.168.10.100 should be answered by the requested IP addresses
correctly.
2. Sent "Ping" to IP addresses 192.168.10.101 and 192.168.10.102 should be answered by the re-
quested IP addresses as "Destination host unreachable".
Note:
1. If you perform the ping test using a PC please check the PC's firewall configuration to ensure that ping
requests and echoes are allowed.
2. Keep in mind that every device which will be used for ping testing needs an entry for the standard gateway
(IP address is pointing to the Router of the PC's network)