Fig. 3-15 Dip Switch To Change-Over Between 50/60 Hz; Fig. 3-16 Mode Of Operation Of The 50/60 Hz Dip Switch In Conjunction With P0100; 50/60 Hz Setting - Siemens MICROMASTER 420 Operating Instructions Manual

0.12 kw - 11 kw
Hide thumbs Also See for MICROMASTER 420:
Table of Contents

Advertisement

Issue 07/04
3.5.1

50/60 Hz setting

The frequency setting made in the factory can be adapted to the North American
market, without requiring any parameterization using an operator panel or PC tool
using the 50/60 Hz DIP switch (refer to Fig. 3-15).
Fig. 3-15
The switch determines the value of parameter P0100 corresponding to the
following diagram (refer to Fig. 3-16). Besides P0100 = 2, after the power supply
voltage has been switched-in, the 50/60 Hz DIP switch determines the 50/60 Hz
setting (value of parameter P0100).
Fig. 3-16
MICROMASTER 420
Operating Instructions
6SE6400-5AA00-0BP0
DIP switch to change-over between 50/60 Hz
Power
cycle
yes
P0100 = 2
?
no
no
DIP2 = OFF
?
yes
Power in kW
Frequency 50 Hz
Frequency 60 Hz
P0100 = 0
Mode of operation of the 50/60 Hz DIP switch in conjunction with P0100
60 Hz
50 Hz
50/60 Hz DIP switch
for frequency setting
commissioning
P0010 = 1
yes
P0100 = 2
no
P0100 = 1
Power in kW
Power in hp
Frequency 60 Hz
P0100 = 2
P0100 = 1
3 Functions
Quick
?
no
?
yes
61