Installation troubleshooting

Procedure A-2: Fan unit test failure

...................................................................................................................................................................................................................................
Overview
The procedure described below should be performed if one of the following failures
can be observed:
• The "PWR ON" LED does not light up on the fan unit.
Procedure 1 must be used in this case.
• Not all fans are running.
Procedure 2 must be used in this case.
• The air flow direction is not from bottom to top.
Procedure 2 must be used in this case.
Procedure 1
Proceed as follows if the "PWR ON" LED does not light up on the fan unit:
...................................................................................................................................................................................................
Switch all circuit breakers on the subrack backplane (see chapter 5,
1
switching" (p.
...................................................................................................................................................................................................
Replace all affected fan power cables between the Power Interfaces and the fan unit.
2
Make sure that the cables are tight afterwards.
...................................................................................................................................................................................................
Switch all circuit breakers on the subrack backplane to the ON position (="I").
3
IF ...
the "PWR ON" LED does not light
up on the fan unit,
the "PWR ON" LED lights up on
the fan unit,
E
N D
O F
...................................................................................................................................................................................................
...................................................................................................................................................................................................................................
A-4
5-5)) to the OFF position (="O").
S T E P S
Alcatel-Lucent - Proprietary
See notice on first page
THEN ...
switch all circuit breakers on the subrack
backplane to the OFF position (="O") and
replace the affected fan unit.
END OF STEPS