6.6 "Interfaces" menu
Note
In WDS operation, the following restrictions apply to all access points involved:
• All access points that will communicate with each other must use the same channel, the
same transmission procedure and the same data rate.
• You can select either WEP or WPA(2)-PSK as the encryption method.
You configure the security settings in the assigned VAP interface: "Security > WLAN >
Basic"
You cannot use authentication with a RADIUS server for a WDS connection.
• In the IEEE 802.11h transmission mode, it is not practical to select the WDS mode. In
WDS mode, all access points must use the same channel. If a signal from a primary user
is detected by an access point, the channel is changed automatically and the existing
connection is then terminated.
Procedure
1. Select the required VAP interface from the "Connection over" drop-down list.
2. Select the entry "WDS ID" in the "Partner ID Type" drop-down list.
3. Enter the WDS ID of the WDS partner in the "Partner WDS ID" input box. The "MAC
Address" input box is grayed out.
4. Click the "Set Values" button.
292
SCALANCE W780/W740 to IEEE 802.11n Web Based Management
Configuration Manual, 08/2018, C79000-G8976-C267-13