Technical Data; Conformity; Standards; Operating Conditions - Burkert 8653 AirLINE Field Operating Instructions Manual

Field module for pneumatic systems
Hide thumbs Also See for 8653 AirLINE Field:
Table of Contents

Advertisement

6

Technical daTa

6.1

Conformity

The device conforms to the EU directives as per the EU Declaration of Conformity (if applicable).
6.2

Standards

The applied standards, which are used to demonstrate conformity with the directives, are listed in the EU
type examination certificate and/or the EU Declaration of Conformity (if applicable).
6.3

Operating conditions

note
Use safety extra-low voltage in accordance with protection class 3 VDE 0580.
Type of condition
Ambient temperature
Storage temperature
Compressed air quality
Nominal operating
mode
Operating voltage
Protection class
Current consumption
6.4

General technical data

Valve slots
Degree of protection
6.4.1

Pneumatic slide valve type 6534

Circuit function (CF)
Flow rate Q
Nn
14
permitted range
–10...+55 °C
–10...+60 °C
ISO 8573-1:2010, Class 7.4.4
Continuous operation (100% duty cycle)
24 V
± 10% residual ripple at fieldbus interface 1 Vss
3 in accordance with VDE 0580
≤ 260 mA
4
IP65/67
2 x c NC (normally closed)
2 x 3/2-way
2 x d NO (normally open)
2 x 3/2-way
Up to 310 l
/min
N
(see data sheet for exact flow rate values for the various circuit functions)
english
Type 8653
Technical data
h
5/2-way monostable
Z
5/2-way bistable
(on request)
l
5/3-way locked
(on request)
m
5/3-way
pressurised
(on request)
n
5/3-way exhausted
(on request)