Type 8653
Operation
13.3

LED status display

The LED for displaying the device status changes colour and status similar to NAMUR NE 107.
If several device statuses exist simultaneously, the device status with the highest priority is displayed. The
priority depends on the severity of the deviation from standard operation (red = failure = highest priority).
Status display in accordance with NE 107, edition 2006-06-12
Colour Colour
Description
code
red
5
Failure, error or
malfunction
orange
4
Function
check
yellow
3
Out of
specification
blue
2
Maintenance
required
green
1
Diagnostics
active
white
0
Diagnostics
inactive
Table 4:
Device status indication based on NAMUR NE 107
Meaning
Standard operation is not possible due to malfunctioning in the
device or peripheral devices.
An internal function/check is performed. This status is exited auto-
matically after a certain time. No user intervention required.
Deviation of parameters (e.g. different address/node ID used).
Check parameters.
The device is in standard operation mode, however, a function
could soon be restricted.
Perform device maintenance.
Device is operating perfectly. Status changes are indicated in
different colours.
Messages are transmitted by a fieldbus if connected.
Device is switched on. Status conditions are not displayed.
Messages are not displayed in the message list or transmitted via
a potentially connected fieldbus.
Device operates within its specifications.
english