Type 8653
Electrical connection
8
elecTrical cOnnecTiOn
Caution
risk of injury from electric shock.
Before working on the device or system, switch off the power supply. Secure against reactivation.
►
Observe applicable accident prevention and safety regulations for electrical equipment.
►
risk of injury due to incorrect electrical connection work.
The electrical connection work should be carried out by fully trained personnel only.
►
Use suitable tools to establish the electrical connection.
►
Further information on cabling büS networks can be found under the following link:
Guide for planning of büS networks
note
To ensure electromagnetic compatibility (EMC):
Only use shielded cables.
►
Connect the functional earth (see chapter "8.1" on page 22).
►
Assignment of circular plug M12, 5-pole, A-coded
View of pins
4
5
1
3
2
Table 1:
Assignment of circular plug M12, 5-pole
pin
Assignment
1
Shielding
2
Supply voltage 24 V
3
GND
4
CAN_H (büS connection)
5
CAN_L (büS connection)
english