Type 8653

Electrical connection

8
elecTrical cOnnecTiOn
Caution
risk of injury from electric shock.
Before working on the device or system, switch off the power supply. Secure against reactivation.
Observe applicable accident prevention and safety regulations for electrical equipment.
risk of injury due to incorrect electrical connection work.
The electrical connection work should be carried out by fully trained personnel only.
Use suitable tools to establish the electrical connection.
Further information on cabling büS networks can be found under the following link:
Guide for planning of büS networks
note
To ensure electromagnetic compatibility (EMC):
Only use shielded cables.
Connect the functional earth (see chapter "8.1" on page 22).
Assignment of circular plug M12, 5-pole, A-coded
View of pins
4
5
1
3
2
Table 1:
Assignment of circular plug M12, 5-pole
pin
Assignment
1
Shielding
2
Supply voltage 24 V
3
GND
4
CAN_H (büS connection)
5
CAN_L (büS connection)