Step 4: Verifying Proper Power Optimiser
Connection
When a module is connected to a power optimiser, the power optimiser outputs a safe voltage of 1V 
(±0.1V). Therefore, the total string voltage should equal 1V times the number of power optimisers 
connected in series in the string. For example, if 10 power optimisers are connected in a string, then 10V 
should be produced.
Make sure the PV modules are exposed to sunlight during this process. The power optimiser will only   t urn 
ON if   t he PV module provides at least 2W. 
In SolarEdge systems, due to the introduction of poweroptimisers between the PV modules and the 
inverter, the short circuit current I
those in traditional systems. 
For more information about the SolarEdge   s ystem's string voltage and current, refer to 
the V
 and I
 in SolarEdge Systems Technical Note, available on the SolarEdge website at: 
OC
SC
https://www.solaredge.com/sites/default/files/isc_and_voc_in_solaredge_sytems_
technical_note.pdf . 
To verify proper power optimiser connection:
Measure the voltage of each string individually before connecting it to the other strings or to the inverter. 
Verify correct polarity by measuring the string polarity with a voltmeter. Use a voltmeter with at least 
0.1V measurement accuracy.
NOTE
Since the inverter is not yet operating, you may measure the string voltage and verify correct polarity
on the DC wires inside the Connection Unit.
For troubleshooting power optimiser operation problems, refer to Power Optimizer Troubleshooting  on 
page 72.
-Three Phase Inverter with Synergy Technology Installation MAN-01-00402-1.4
 and the open circuit voltage V
SC
Chapter 2: Installing the Power Optimisers
 hold different meanings from 
OC
21