Mounting and Connecting the Primary and Secondary Unit(s)
 6.  Mount   t he Primary Unit:
 a.  Lift the Primary Unit from its sides. 
 b.  Align the two indentations in the   e nclosure with the two triangular mounting tabs of the bracket, 
and lower the unit until it rests on the bracket evenly (see Figure 20).
 c.  Insert the supplied screw through the right side of the heat sink and into the bracket.
 7.  Mount the Secondary Unit(s):
 
There is no specific order for hanging the Secondary Units.
l
When installing a 2 unit inverter, mount the Secondary Unit to the left of the Primary Unit.
 
Lift the Secondary Unit(s) from the sides, or hold it at the top and bottom of the unit to lift 
l
into place.
 
Align the two indentations in the enclosure with the two triangular mounting tabs of the 
l
bracket, and lower the   u nit until it rests on the bracket evenly   ( see Figure 20).
 
Insert one of the supplied screws through the outer side of the heat sink and into the bracket. 
l
Tighten the screws with a torque of 4.0N*m / 2.9 lb.*ft.
 8.  Secure the Connection Unit to the wall:
 
Mark the location of the bracket screw and drill the hole
l
 
Fasten the bracket using a standard bolt
l
 
Verify that the bracket is firmly attached to the mounting surface .
l
 
32
-Three Phase Inverter with Synergy Technology Installation MAN-01-00402-1.4
Figure 20: Hanging units
Figure 21: Connection Unit bracket