SolarEdge SE66.6KUS Installation Manual page 9

Three phase inverter with synergy technology
Hide thumbs Also See for SE66.6KUS:
Table of Contents

Advertisement

IMPORTANT INVERTER SAFETY INSTRUCTIONS
WARNING
Before operating the inverter, ensure that the inverter is grounded properly.
AVERTISSEMENT!
Avant d'utiliser l'onduleur monophasé, est correctement mis à la terre.
WARNING!
The inverter input and output circuits are isolated from the enclosure. This system does not include an
isolation transformer and should be installed with an ungrounded PV array in accordance with the
requirements of NEC Articles 690.35 and 690.43 National Electric Code, ANSI/NFPA 70, 2011 (and
Canadian Electrical Code, Part I, for installations in Canada).
Equipment grounding is the responsibility of the installer and must be performed in accordance with all
applicable Local and National Codes.
AVERTISSEMENT!
Les circuits d'entrée et de sortie de l'onduleur sont isolés de l'enveloppe. Ce système n'inclut pas
d'isolation galvanique (transformateur) et devra être installé sans mise à la terre du champ PV et en
accord avec les articles 690.35 et 690.43 du National Electric Code (NEC), ANSI/NFPA 70, 2011 (et du
Code Electrique Canadien, Partie 1, pour les installations faites au Canada).
La mise à la terre des équipements est la responsabilité de l'installateur et doit être faite en accord avec
les toutes les règles locales et nationales applicables.
WARNING!
Opening the inverter and repairing or testing under power must be performed only by qualified service
personnel familiar with this inverter.
AVERTISSEMENT!
L'unité ne doit être ouverte que par un technicien qualifié dans le cadre de l'installation et de la
maintenance.
WARNING!
The three phase SE66.6KUS and SE100KUS inverters must be connected only to a dedicated AC
branch circuit with a maximum Overcurrent Protection Device (OCPD) of 120A or 180A respectively.
AVERTISSEMENT!
Les onduleurs triphasés SE66.6kUS et SE100kUS doivent être connectés à une ligne appareil AC
dédiée avec un appareil de protection de sur-courant (OCPD-OverCurrent Protection Device) de
maximum 120A ou 180A respectivement.
WARNING!
SafeDC complies with IEC60947-3 when installing the system with a worst case SafeDC voltage (under
fault conditions) < 120V.
The worst case voltage is defined as: Voc,max+ (String Length-1)*1V,where:
Voc,max = Maximum Voc (at lowest temperature) of the PV module in the string (for a string with
l
multiple module models, use the max value)
String Length = number of power optimisers in the string
l
8
-Three Phase Inverter with Synergy Technology Installation MAN-01-00402-1.4