6.6.3 Reset a latched alarm

A latched alarm is one that cannot automatically reset itself when the triggering event has cleared.
Note: Operator or higher access level is required (optional, see Commissioning, Buzzer Activation and Button
Password Protection).
A latched alarm can be reset in three ways by:
1) Touching the Reset button for >3 seconds. This will reset ALL latched alarms, faults and warnings,
provided that the triggering event has cleared. It will also reset any latched relay outputs.
2) Selecting Menu>Maintenance>Reset alarms/Faults. This will reset all latched events for the channel,
provided that the input signal has returned to Normal status.
3) Holding the Remote reset switch for >3 seconds. TPPL has the option of adding a remote acknowledge /
reset switch up to 500 m away from the Controller, but care should be taken to prevent unauthorised
people accessing the switch.
A gas detector may indicate that the gas concentration in its vicinity has dropped to a safe level, but this does
not mean that a dangerous atmosphere doesn't persist elsewhere in that area. Do not reset the alarms until the

6.7 Faults and Warnings

6.7.1 View Faults and Warnings

Detailed information about active Faults and Warnings can be viewed:
1) From the Input and output screen, select either the Fault (yellow filter) icon, or the Warning (blue filter)
icon. The screen will show a filtered list of only the active Faults or Warnings.