Section 12
Testing functionality by secondary injection
1.
Set
2.
Apply the fault condition, including start of CCRBRF, well above the set current value.
3.
Verify that no re-trip, but back-up trip is achieved after set time.
Checking the re-trip with current check,
1.
Set
2.
Apply the fault condition, including start of CCRBRF, well above the set current value.
3.
Verify that re-trip is achieved after set time
4.
Apply the fault condition, including the start of CCRBRF, with the current below the set
current value.
5.
Verify that no re-trip, and no back-up trip is obtained.
Checking re-trip without current check
1.
Set
2.
Apply the fault condition, including start of CCRBRF, well above the set current value.
3.
Verify that re-trip is achieved after the set time
4.
Apply the fault condition, including start of CCRBRF, with current below set current value.
5.
Verify that re-trip is achieved after set time
12.5.9.5
Verifying the back-up trip mode
In the cases below it is assumed that
Checking that back-up tripping is not achieved at normal CB tripping
Use the actual tripping modes. The case below applies to re-trip with current check.
1.
Apply the fault condition, including start of CCRBRF, with phase current well above set
value
2.
Interrupt the current, with a margin before back-up trip time,
of re-trip command.
3.
Check that re-trip is achieved, if selected, but no back-up trip is obtained.
The normal mode
applicable cases the modes
which corresponds to the actual case.
Checking the case
It is assumed that the earth-fault current setting
1.
Set
2.
Apply the fault condition, including start of CCRBRF, with one-phase current below set
IP> but above IN> . The residual earth-fault should then be above set IN> .
3.
Verify that back-up trip is achieved after set time. If selected, re-trip should also appear.
4.
Disconnect AC and START input signals.
Checking the case
The earth-fault current setting
1.
Set
2.
Apply the fault condition, including start of CCRBRF, with one-phase current above set
IP> and residual (earth fault) above set IN> .
3.
Verify that back-up trip is achieved after set time. If selected, re-trip should also appear.
166
RetripMode = Retrip Off .
RetripMode = CB Pos Check .
RetripMode = No CBPos Check .
IP> .
BuTripMode = 1 out of 3 should have been verified in the tests above. In
1 out of 4 and 2 out of 4 can be checked. Choose the mode below,
BuTripMode = 1 out of 4
BuTripMode = 1 out of 4 .
BuTripMode = 2 out of 4
IN> may be equal to or below phase-current setting IP> .
BuTripMode = 2 out of 4 .
RetripMode = CB Pos Check
t1 and back-up trip after time t2
t1 , and the back-up trip after time t2 .
t1 , but no back-up trip is obtained.
FunctionMode = Current is selected.
IN> is below phase current setting IP> .
1MRK 502 067-UEN B
M12104-48 v6
M12104-58 v8
M12104-146 v5
M12104-150 v7
t2 . It may be made at issue
M12104-165 v6
M12104-179 v7