Remote Communication; Binary Signal Transfer Binsignreceive, Binsigntransm - ABB RELION REG670 Commissioning Manual

Generator protection
Hide thumbs Also See for RELION REG670:
Table of Contents

Advertisement

1MRK 502 067-UEN B
12.15

Remote communication

12.15.1

Binary signal transfer BinSignReceive, BinSignTransm

Prepare the IED for verification of settings as outlined in section
settings".
To perform a test of Binary signal transfer function (BinSignReceive/BinSignTransm), the
hardware (LDCM) and binary input and output signals to transfer must be configured as
required by the application.
There are two types of internal self supervision of BinSignReceive/BinSignTransm
The I/O-circuit board is supervised as an I/O module. For example it generates FAIL if the
board is not inserted. I/O-modules not configured are not supervised.
The communication is supervised and the signal COMFAIL is generated if a
communication error is detected.
Status for inputs and outputs as well as self-supervision status are available from the local
HMI under
Self-supervision status: Main menu/Diagnostics/Internal events
Status for inputs and outputs: Main menu/Test/Function status, browse to the function
group of interest.
Remote communication related signals: Main menu/Test/Function status/
Communication/Remote communication
Test the correct functionality by simulating different kind of faults. Also check that sent and
received data is correctly transmitted and read.
A test connection is shown in figure 68. A binary input signal (BI) at End1 is configured to be
transferred through the communication link to End2. At End2 the received signal is configured
to control a binary output (BO). Check at End2 that the BI signal is received and the BO
operates.
Repeat the test for all the signals configured to be transmitted over the communication link.
Commissioning manual
Testing functionality by secondary injection
"Preparing the IED to verify
Section 12
SEMOD53601-1 v1
M14951-2 v5
229

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 670 series

Table of Contents