All trip outputs (TRL1, TRL2, TRL3) and functional outputs TRIP and TR3P must be active
and stay active after each fault, CLLKOUT should be set.
10.
Reset the lockout.
All functional outputs should reset.
11.
Deactivate the TRIP signal lockout function, set
lockout function, set
12.11.1.5

Completing the test

Continue to test another function or end the test by changing the
Restore connections and settings to their original values, if they were changed for testing
purposes.
12.11.2

Integrator TIGAPC

The integrator function TIGAPC can be tested by connecting a binary signal to the input of the
function and applying pulses to the function. Normally the Integrator will be tested when
testing the function the integrator is connected to, such as reverse power, loss of excitation
and pole slip. When the function is configured, test it together with the function that operates
it.
12.11.2.1
Completing the test
Continue to test another function or end the test by changing the Test mode setting to
Restore connections and settings to their original values, if they were changed for testing
purposes.
12.12

Monitoring

12.12.1

Gas medium supervision SSIMG

Prepare the IED for verification of settings as outlined in section
supervision for alarm and lock out conditions"
chapter.
Check that the input logical signal BLOCK is logical zero and that on the local HMI, the logical
signals PRES_ALM, PRES_LO, TEMP_ALM and TEMP_LO are equal to logical zero.
12.12.1.1

Testing the liquid medium supervision for alarm and lock out conditions

1.
Connect binary inputs to consider gas pressure and gas density to initiate the alarms.
2.
Consider the analogue pressure input PRESSURE to initiate the alarms.
3.
Gas pressure lock out input can be used to set PRES_LO signal, check the signal status in
local HMI under Main menu/Test/Function status/Monitoring/Gas medium supervision
SSIMG/PRES_LO
4.
Reduce the pressure level input below
local HMI under Main menu/Test/Function status/Monitoring/Gas medium supervision
SSIMG/PRES_ALM
5.
Activate BLOCK binary input, the signals PRES_ALM, PRES_LO should disappear.
6.
Reset the BLOCK binary input.
Commissioning manual
AutoLock = Off .
and section
PresAlmLimit , check for PRES_ALM signal status in
Testing functionality by secondary injection
TripLockout = Off and the automatic
TestMode setting to Off .
GUID-D18B2BCA-A79B-4B04-860C-BE2122FECEA7 v2
GUID-5CD0314D-7D02-477E-BC16-12C82534E72D v2
GUID-0A83B4D5-51FF-43CB-8DC7-AFCEA2BC7B69 v1
"Testing the liquid medium
"Completing the test"
GUID-768DAAC8-F89D-4401-B86D-9B26FD7224F6 v1
Section 12
SEMOD54375-203 v6
Off .
SEMOD53581-1 v1
in this
223