Section 12
Testing functionality by secondary injection
IEC09000735 V3 EN-US
Figure 36: Operating characteristic for phase selection function, forward direction
Table 20: Test points for phase-to-phase loops L1–L2 (Ohm/phase)
Test point
1
2
3
4
5
6
Table
20
12.4.2.1

Measuring the operating limit of set values

Procedure:
108
X
1
4
85%
X1
ArgNegRes
50% RLdFw
0.5·RFFwPP
phase-to-phase faults
Reach
Value
X
X1
R
0
X
0
R
RLdFw
R
0,5·RFFwPP
X
0.85·X1
R
0.85·X1·1/tan(60°)+0.5 RFFwPP
X
0.85·X1
R
-0.85·X1·tan (AngNegRes-90°)
X
0.5·RFFwPP·tan (ArgLd)
R
0.5·RFFwPP
X
-0.5·RLdFw·tan (ArgDir)
R
0.5·RLdFw
is used together with figure 36.
W
(
/
phase
)
5
60°
2
7
6
ArgDir
Comments
When RLdFw < 0,5·RFFwPP
When RLdFw > 0,5·RFFwPP
R=0.491·X1+0.5 RFFwPP
Can be limited by RFFwPP
Only when RLdFW < RFFwPP
3
ArgLd
W
(
/
phase
)
R
IEC09000735-3-en.vsd
Commissioning manual
1MRK 502 067-UEN B