ABB RELION REG670 Commissioning Manual page 147

Generator protection
Hide thumbs Also See for RELION REG670:
Table of Contents

Advertisement

1MRK 502 067-UEN B
The trajectory of the impedance traverses the lens characteristic in zone 1
Preliminary steady state test at 50 Hz
Go to Main menu/Test/Function status/Impedance protection/OutOfStep(78,Ucos)/
OOSPPAM(78,Ucos):1/Outputs to check the available service values of the function block
OOSPPAM.
Apply the following three-phase symmetrical quantities (the phase angle is related to
phase L1):
V
ts
EQUATION14066 V1 EN-US
V
EQUATION14058 V1 EN-US
frequency of V
I
50
s
EQUATION14059 V1 EN-US
I
50s
frequency of
It
fs
EQUATION14062 V1 EN-US
I
tfs
frequency of
Check that the service values (VOLTAGE, CURRENT, R(%), X(%)) are according to the
injected quantities and that ROTORANG is close to 3.14 rad. For this particular injection
the service values are:
Note that these values identify a point inside the lens characteristic in zone 1, that is close
to the boundary between zone 1 and zone 2. The START is issued, but no TRIP is
performed.
Execution of the dynamic test
The test may be performed by using two states of a sequence tool that is a basic feature of
test sets.
State 1: pre-test condition.
Steady voltage and current are applied in order to get a steady high impedance, that is a
point in the plane R-X which is far away from the lens characteristic. Define the following
three-phase symmetrical quantities (the phase angle is related to phase L1):
Commissioning manual
V
VT s
,
V
0 9
.
0 9 1435
.
=
×
×
=
×
t RZ
,
1
V
VT p
,
ForwardX
arctan
=
 =
ts
ForwardR
= 50 Hz
ts
I
1
CTs
I
10459
=
×
=
×
50
I
9000
CTp
= 0º
I
= 50 Hz
50s
I
1
CTs
I
10459
=
×
=
×
tf
I
9000
CTp
= 0º
I
= 50 Hz
tf
VOLTAGE = 1.29 kV
CURRENT = 20918 A
R = 0.89%
X=6.42%
ROTORANG = -3.04 rad
0 1
.
V
9 36
.
×
=
13 8
.
59 33
.
arctan
82. . 14°
 =
8 19
.
= .
1 162
A
1 162
.
A
=
Testing functionality by secondary injection
GUID-12F82DD8-A4CE-48C9-944B-0CF3B3F6C9F9 v1
GUID-AA953F5F-2389-4F05-8BBD-D8DC9AF3B0E4 v1
(Equation 47)
(Equation 48)
(Equation 49)
(Equation 50)
GUID-98707DB3-9A1A-4458-9704-25F8FCB94B79 v1
Section 12
141

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 670 series

Table of Contents