Testing

The protection function uses injection of an ac voltage to the generator field circuit. The
COMBIFLEX voltage injection unit RXTTE4, Part No 1MRK 002 108-AB contains a voltage
transformer with a primary winding for connection to 120 or 230 V, 50 or 60 Hz supply voltage.
From the secondary winding of this internal voltage transformer approximately 40 V AC is
injected via series capacitors and resistors into the rotor circuit. The injected voltage is fed to
a voltage input of the REG670 IED. The current caused by the injection is fed to a current input
of the REG670 IED via a current transformer, which is amplifying the current ten times, as
shown in figure 55.
IEC06000498 V1 EN-US
Figure 55: Ten times amplification of current via a current transformer
The test described in steps
Procedure
1.
The test should be prepared with a switch connected between the output of RXTTE4
(221) and the station earth. Initially this switch is open.
2.
First the 120 (230) V input to RXTTE4 is disconnected. This should give a signal from
REG670 that the injection voltage is low.
3.
Reconnect the 120 (230) V input and check that the low injection voltage signal resets.
Commissioning manual
Generator rotor winding
G
Connection to be done
by the panel builder
REG 670
1
to
6
can be done with the generator at stand-still situations.
RXTTE 4
221 222
421
I
428
324
U
325
Testing functionality by secondary injection
Optional
external resistor
313
230 V AC
314
120 V AC
315
0
en06000498.vsd