Cable Sizes For 640-1100 V Dc (525-690 V Ac); Cable Stripping Lengths - Danfoss VACON NX FI6 Operating Manual

Table of Contents

Advertisement

Operating Guide | VACON® NX Inverters FI4-FI8
12.3.4 Cable Sizes for 640–1100 V DC (525–690 V AC)
Table 28: Cable Sizes for 640–1100 V DC (525–690 V AC)
Enclosure
Drive type
size
FI6
NXI_0004 6–0007 6
NXI_0010 6–0013 6
NXI_0018 6
NXI_0022 6
NXI_0027 6–0034 6
FI7
NXI_0041 6
NXI_0052 6
FI8
NXI_0062–0080 6
NXI_0100 6

12.4 Cable Stripping Lengths

See
illustration 44
for parts of cables to be stripped and check the corresponding stripping length in the table.
116 | Danfoss A/S © 2019.07
I
[A]
Supply cable
Motor cable Cu
L
2
Cu [mm
]
[mm
3–7
2*2.5
3*2.5+2.5
10–13
2*2.5
3*2.5+2.5
18
2*4
3*4+4
22
2*6
3*6+6
27–34
2*10
3*10+10
41
2*100
3*10+10
52
2*16
3*16+16
62–80
2*25
3*25+16
100
2*35
3*35+16
Main terminal cable
2
2
]
[mm
]
2.5–50 Cu
6–50 Al
2.5–50 Cu
6–50 Al
2.5–50 Cu
6–50 Al
2.5–50 Cu
6–50 Al
2.5–50 Cu
6–50 Al
2.5–50 Cu
6–50 Al
2.5–50 Cu
6–50 Al
25–95 Cu/Al
Specifications
Earth terminal ca-
2
ble [mm
]
2.5–35
2.5–35
2.5–35
2.5–35
2.5–35
6–50
6–50
25–95
AQ299433367205en-000101 / DPD00908

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vacon nx fi4Vacon nx fi7Vacon nx fi8

Table of Contents