Operating Guide | VACON® NX Inverters FI4-FI8
Troubleshooting
Change the OPTAF board.
12.10.33 Fault 8 - System fault, Subcode S43 - OPTAF: Test pulse high is not detected on thermistor
Cause
Single hardware problem detected in the thermistor input.
Troubleshooting
Change the OPTAF board.
12.10.34 Fault 8 - System fault, Subcode S44 - OPTAF: STO channel 1 is not active, even if the analog
input supervision indicates
Cause
Single hardware problem detected in Safe Disable inputs or in the thermistor input.
Troubleshooting
Change the OPTAF board.
Change the control board.
12.10.35 Fault 8 - System fault, Subcode S45 - OPTAF: STO channel 2 is not active, even if the analog
input supervision indicates
Cause
Single hardware problem detected in Safe Disable inputs or in the thermistor input.
Troubleshooting
Change the OPTAF board.
Change the control board.
12.10.36 Fault 8 - System fault, Subcode S46 - OPTAF: Thermistor or analog input is not set, even if
STO is active
Cause
Single hardware problem detected in Safe Disable inputs or in the thermistor input.
Troubleshooting
Change the OPTAF board.
Change the control board.
134 | Danfoss A/S © 2019.07