Operating Guide | VACON® NX Inverters FI4-FI8
3 The rubber grommets GD21 (FR7/FI7 IP54/UL Type 12),
3 pieces / (FR8/FI8), 6 pieces
Illustration 7:
Contents of the Accessories Bag for FR7-FR8/FI7-FI8

4.2 Storing the Product

Context:
If the product has to be stored before installing it, follow these instructions.
Procedure
1. If the AC drive must be stored before using it, make sure that the ambient conditions agree to the following:
Storage temperature: -40...+70° C (-40...+158° F)
Relative humidity: 0–95%, no condensation
2. If the AC drive must be kept in storage for a long time, connect the power to the AC drive each year. Keep the power on for a
minimum of 2 hours.
3. If the storage time is more than 12 months, charge the electrolytic DC capacitors with caution. To reform the capacitors, obey the
instructions in
10.2 Reforming the
We do not recommend a long storage time.

4.3 Lifting the Product

Context:
To get information on how to lift the AC drive safely, speak to the factory or the local distributor.
Prerequisites:
The weights of AC drives of different enclosure sizes are different. It can be necessary to use a lifting device to move the drive from its
package.
Procedure
1. Check the weight of the inverter, see
2. To lift the AC drives larger than FR7/FI7 out of the package, use a jib crane.
3. After lifting the drive, check for signs of damage on the drive.

4.4 Using the Product Modified Label

Context:
In the accessories bag, there is also a "product modified" label. The function of the label is to tell the service personnel about the
changes that are made in the AC drive.
28 | Danfoss A/S © 2019.07
Capacitors.
12.1 Weights of the
Inverter.
Receiving the Delivery
AQ299433367205en-000101 / DPD00908

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VACON NX FI6 and is the answer not in the manual?

This manual is also suitable for:

Vacon nx fi4Vacon nx fi7Vacon nx fi8

Table of Contents