10 Maintenance

10.1 Maintenance Schedule

In normal conditions, VACON
conditions, load, line power, and process control must be within specifications, determined by the manufacturer.
To make sure that the inverter operates correctly and has a long life, we recommend doing regular maintenance. Refer to the table for
maintenance intervals.
We also recommend recording all actions and counter values with dates and time to follow up of maintenance.
Table 16: Maintenance Intervals and Tasks
Maintenance in-
Maintenance task
terval
Reform the capacitors (see
12 months
(1)
If the unit was in store for much longer than 12 months and the capacitors were not charged, speak to the
factory to get instructions before connecting the power.
Do a check of the tightening torques of the terminals.
(2)
6–24 months
Clean the heat sink.
Clean the cooling channel.
Make sure that the cooling fan operates correctly.
Make sure that there is no corrosion on the terminals, the busbars, or other surfaces.
If there is cabinet installation, do a check of the door filters.
5–7 years
Change the cooling fans:
the main fan
the fan of the LCL filter
the internal IP54 (UL Type 12) fan
the cabinet cooling fan/filter
5–10 years
Change the DC bus capacitors, if the DC voltage ripple is high.
1
If the unit is kept in store.
2
The interval is different in different environments.

10.2 Reforming the Capacitors

Context:
The electrolytic capacitors in the DC link rely on a chemical process to provide the insulator between the two metal plates. This process
can degrade over a period of years when the drive has been non-operational (stocked). The result is that the working voltage of the DC
link gradually falls.
The correct course of action is to ensure that the insulation layer of the capacitor is 'reformed' by the application of a limited current
using a DC supply. Current limiting ensures that the heat generated within the capacitor is kept at a sufficiently low level to prevent
any damage.
104 | Danfoss A/S © 2019.07
®
NX Inverters are maintenance-free. To maintain trouble-free operation of the unit, environmental
10.2 Reforming the
Capacitors)
Maintenance
AQ299433367205en-000101 / DPD00908

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vacon nx fi4Vacon nx fi7Vacon nx fi8

Table of Contents