VLT® Automation Drive FC302
Recommended Drive settings for hoist applications with drive sw version 7.29 and higher
Par. 1-50 Motor Magnetization At Zero
Speed <<[110-130%]>>
Par. 1-53 Model Shift Frequency
[8-10Hz]
Par. 1-66 Min Current At Low Speed
[100-150%]
Par. 1-67 Load Type
<<Active Load>> [1]
Par. 1-72 Start Function
<<Hoist Mech Brake Rel.>> [6]
Par. 1-80 Function At Stop
<<Coast or Premag>> [0 or 3]
Par. 1-81 Min Speed for Function At
Stop [>5rpm... n
]
slip
Par. 2-21 Activate Brake Speed
[100...150rpm]
Par. 2-23 Activate Brake Delay
[0,2...0,5s]
Par. 1-00 Configuration Mode
<<Speed Open Loop>> [0]
Par. 1-01 Motor Control Principle
<<Flux Sensorless>> [2]
Par. 1-03 Torque Characteristics
<<Constant Torque>> [0]
Par. 1-04 Overload Mode
<<High torque>> [0]
Par. 1-06 Clockwise Direction
<<Normal>> [0]
Par. 1-47 Torque Calibration
<<1st start after pwr-up>> [1]
no
Cone rotor
Start with factory setting value and increase it if
the start behaviour is not good enough
Start with a value around 1s and reduce it
afterwards
Make sure that the hoisting direction is in
clockwise motor direction
Minimum slip speed
Premag is prefered but not always possible
Cone rotor
no
Start
no
Speed feedback
Par. 1-20 Motor Power [kW]
Par. 1-22 Motor Voltage [V]
Par. 1-23 Motor Frequency [Hz]
Par. 1-24 Motor Nominal Current [A]
Par. 1-25 Motor Nominal Speed [rpm]
Par. 1-29 Automatic Motor Adaptation
[1]
no
Speed feedback
yes
Par. 1-53 Model Shift Frequency
[8-10Hz]
Par. 1-66 Min Current At Low Speed
[120-150%]
Par. 1-67 Load Type
<<Active Load>> [1]
Par. 1-71 Start Delay
[0,1...0,5s]
Par. 1-72 Start Function
<<VVC+/Flux Clockwise>> [5]
Par. 1-74 Start Speed
[100...400rpm]
Par. 1-76 Start Current
[nominal motor current A]
Par. 1-80 Function At Stop
<<Coast>> [0]
Par. 1-81 Min Speed for Function At
Stop [100...500rpm]
Par. 1-90 Motor Thermal Protection
<<Thermistor Trip>>[2]
Par. 1-91 Motor External Fan
if available [1]
Par. 1-93 Thermistor Resource
Analog Input 53 [1] or
Analog Input 54 [2]
Par. 2-11 Brake Resistor [Ohm]
Par. 2-12 Brake Power Limit [kW]
Par. 2-13 Brake Power Monitor
<<Trip>> [2]
Par. 2-15 Brake Check <<Trip>> [2]
Par. 2-18 Brake Check Condition <<At
Power Up>> [0]
Speed Closed Loop
yes
Page 1 of 3
yes
Par. 1-00 Configuration Mode
<<Speed Closed Loop>> [1]
Par. 1-01 Motor Control Principle
<<Flux with motor feedback>> [3]
Par. 1-02 Flux Motor Feedback Source
<<24V encoder [1] or MCB102 [2]>>
yes
Par. 1-72 Start Function
<<Hoist Mech Brake Rel.>> [6]
Minimum slip speed
yes
Par. 2-21 Activate Brake Speed
[5...10rpm]
Par. 2-23 Activate Brake Delay
[0,3...5s]
Par. 2-24 Stop Delay
[0,3...1,5s]
Par. 2-25 Brake Release Time
[0,2...1s]

Advertisement

loading
Need help?

Need help?

Do you have a question about the VLT FC302 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Danfoss VLT FC302

  • Page 1 VLT® Automation Drive FC302 Recommended Drive settings for hoist applications with drive sw version 7.29 and higher Start Speed feedback Par. 1-00 Configuration Mode Par. 1-00 Configuration Mode <<Speed Open Loop>> [0] <<Speed Closed Loop>> [1] Par. 1-01 Motor Control Principle Par.
  • Page 2 Par. 2-26 Torque Ref [60…100%] Par. 2-27 Torque Ramp Up Time [0,2…0,5s] If P228 is set to 0 Par. 2-28 Gain Boost Factor Par. 230…233 are [0…4] active Par. 2-29 Torque Ramp Down [0,2…0,5] Par. 2-30 Position P Start Proportional Gain [0,0000…1,0000] Par.
  • Page 3 Par. Group 6-xx Analog In/Out: Because of the high variance how to use the analog i/O's for the different needs it is not part of this sheet. Both analog Inputs terminals 53 and 54 can select either voltage (-10 to 10V) or current (0/4-20mA). Remove power to the frequency converter before changing switch positions. Set switches A53 and A54 to select the signal type. U selects voltage, I selects current.
Save PDF