Operating Guide | VACON® NX Inverters FI4-FI8
I
I L*110%
I L
1 min
Illustration 45:
Low Overload
The high overload means that if 150% of the continuous current (I
minutes must be approximately 92% of I
I
I
H*150%
I
H
1 min
Illustration 46:
High Overload
For more information, refer to the standard IEC61800-2.
Danfoss A/S © 2019.07
I L*110%
9 min
or less. This is to make sure that the output current is not more than I
H
I
H*150%
9 min
t
) is required for 1 minute every 10 minutes, the remaining 9
H
t
Specifications
during the duty cycle.
H
AQ299433367205en-000101 / DPD00908| 119