9.1
Quick setup parameters (Virtual menu, shows when par. 16.2
Code
Parameter
P1.1
Motor nominal voltage
P1.2
Motor nominal frequency
P1.3
Motor nominal speed
P1.4
Motor nominal current
P1.5
Motor cos j (Power Factor)
P1.7
Current limit
P1.15 Torque boost
P1.23 Energy optimization
P2.1
Remote control place 1
P2.2
Start function
P2.3
Stop function
P3.1
Min frequency
P3.2
Max frequency
P3.3
Remote control place 1
frequency reference
selection
P3.4
Preset speed 0
P3.5
Preset speed 1
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
Table 21. Quick setup parameters.
Min
Max
Unit
180
480
30,00
320,00
30
20000
rpm
0,2 × I
2,0 × I
Nunit
Nunit
0,30
1,00
0,2 × I
2,0 × I
Nunit
Nunit
0
1
0
1
0
2
0
1
0
1
0,00
P3.2
P3.1
320,00 Hz
1
Varies
P3.1
P3.2
P3.1
P3.2
1)
Default
ID
V
Varies
110
Hz
50,00/60,00
111
1440/1720
112
A
I
113
Nunit
0,85
120
A
1,5 × I
107
Nunit
0
109
0
666
0
172
0
505
0
506
Hz
0.00
101
Hz
50,00/60,00
102
7
117
Hz
5,00
180
Hz
10,00
105
Note
Energy optimization, the frequency con-
verter search for the minimum current
in order to save energy and lower motor
noise.
56