Quick Setup Parameters - Honeywell HVAC232 Series Applications Manual

Table of Contents

Advertisement

9.1
Quick setup parameters (Virtual menu, shows when par. 16.2
Code
Parameter
P1.1
Motor nominal voltage
P1.2
Motor nominal frequency
P1.3
Motor nominal speed
P1.4
Motor nominal current
P1.5
Motor cos j (Power Factor)
P1.7
Current limit
P1.15 Torque boost
P1.23 Energy optimization
P2.1
Remote control place 1
P2.2
Start function
P2.3
Stop function
P3.1
Min frequency
P3.2
Max frequency
P3.3
Remote control place 1
frequency reference
selection
P3.4
Preset speed 0
P3.5
Preset speed 1
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
Table 21. Quick setup parameters.
Min
Max
Unit
180
480
30,00
320,00
30
20000
rpm
0,2 × I
2,0 × I
Nunit
Nunit
0,30
1,00
0,2 × I
2,0 × I
Nunit
Nunit
0
1
0
1
0
2
0
1
0
1
0,00
P3.2
P3.1
320,00 Hz
1
Varies
P3.1
P3.2
P3.1
P3.2
1)
Default
ID
V
Varies
110
Hz
50,00/60,00
111
1440/1720
112
A
I
113
Nunit
0,85
120
A
1,5 × I
107
Nunit
0
109
0
666
0
172
0
505
0
506
Hz
0.00
101
Hz
50,00/60,00
102
7
117
Hz
5,00
180
Hz
10,00
105
Note
Energy optimization, the frequency con-
verter search for the minimum current
in order to save energy and lower motor
noise.
56

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents