Quick Setup Parameters (Virtual Menu, Shows When Par. 13.1 = 1) - Honeywell SmartVFD COMPACT User Manual

Hvfdcd1b0003 series; hvfdcd1b0005 series; hvfdcd1b0007 series; hvfdcd1b0010 series; hvfdcd1b0015 series; hvfdcd1b0020 series; hvfdcd1b0030 series; hvfdcd3c0005 series; hvfdcd3c0007 series; hvfdcd3c0010 series; hvfdcd3c0015 series; hvfdcd3c0020
Hide thumbs Also See for SmartVFD COMPACT:
Table of Contents

Advertisement

Honeywell
9.1 QUICK SETUP PARAMETERS (VIRTUAL MENU, SHOWS WHEN PAR.
13.1 = 1)
Code
Parameter
Motor nominal
P1.1
voltage
Motor nom. fre-
P1.2
quency
Motor nominal
P1.3
speed
Motor nominal
P1.4
current
P1.5
Motor cos
P1.7
Current limit
P1.15
Torque boost
P2.1
Control place
P2.2
Start function
P2.3
Stop function
P3.1
Min frequency
P3.2
Max frequency
P3.3
I/O reference
P3.4
Preset speed 0
P3.5
Preset speed 1
P3.6
Preset speed 2
P3.7
Preset speed 3
P4.2
Acceleration time
Table 9.1: Quick setup parameters
62-0312—02
Parameters
Min
Max
Unit
180
500
30
320
2000
300
0
0.2 x
1.5 x
I
I
Nunit
Nunit
ϕ
0.30
1.00
0.2 x
2 x
I
I
Nunit
Nunit
0
1
1
3
0
1
0
1
0.00
P3.2
P3.1
320
0
4
0.00
P3.2
0.00
P3.2
0.00
P3.2
0.00
P3.2
0.1
3000
Default
ID
230
V
110
400
Hz
60.00
111
rpm
1440
112
I
A
113
Nunit
0.85
120
1.5 x
A
107
I
Nunit
0
109
1
125
0
505
0
506
Hz
0.00
101
Hz
50.00
102
3
117
Hz
5.00
124
Hz
10.00
105
Hz
15.00
106
Hz
20.00
126
s
1.0
103
42
Note
Check rating plate on the
motor
Check rating plate on the
motor
Default applies for a 4-
pole motor.
Check rating plate on the
motor
Check rating plate on the
motor
0 = Not used
1 = Used
1 = I/O terminal
2 = Keypad
3 = Fieldbus
0 = Ramp 1 = Flying start
0 = Coasting 1 = Ramp
0 = Preset Speeds (0-7)
1 = Keypad Reference
2 = Fieldbus Reference
3 = AI1 (API FULL &
LIMITED)
4 = AI2
(API FULL)
Activated by digital
inputs
Activated by digital
inputs
Activated by digital
inputs
Activated by digital
inputs
Acceleration time from 0
Hz to maximum fre-
quency
9

Advertisement

Table of Contents
loading

Table of Contents