Code
Parameter
P1.17 Motor identification
P1.18 Rs voltage drop
P1.19 Overvoltage controller
P1.20 Undervoltage controller
P1.21 Sine filter
P1.22 Modulator type
feature not used,
leave at default
P1.23 Energy optimization
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
Table 22. Motor settings
Min
Max
Unit
0
1
0,00
100,00
%
0
2
0
1
0
1
0
65535
0
1
Default
ID
Note
0 = not active
0
631
1 = standstill identification
( need run command within 20 s to activate)
2 = ID with run
0,00
662
Voltage drop over motor windings as % of Un at
nominal current. This parameter is adjusted auto-
matically when Identification run is performed.
0 = Disabled
1
607
1 = Enabled: default mode
2 = Enabled: shock load mode
0 = Disable
1
608
1 = Enabled
0
522
0 = Not in use
1 = In use
28928
648
Bit 1 = Discontinuous modulation
Bit 2 = Pulse dropping in over modulation
Bit 6 = Under modulation
Bit 8 = Instantaneous DC voltage compensation
Bit 11 = Low noise
Bit 12 = Dead time compensation
Bit 13 = Flex error compensation
0
666
Energy optimization, the frequency converter
searches for the minimum current in order to save
energy and lower motor noise:
0 = Disabled
1 = Enable