Honeywell HVAC232 Series Applications Manual page 144

Table of Contents

Advertisement

Part number
HVAC402-P55-20
HVAC402-P75-20
HVAC402-1P1-20
HVAC402-1P5-20
HVAC402-2P2-20
HVAC402-3P0-20
HVAC402-4P0-20
HVAC402-5P5-20
HVAC402-7P5-21
HVAC402-11P-21
HVAC402-15P-21
HVAC402-18P-21
* The maximum ambient operating temperature of this drive is 104 °F (40 °C)
NOTE:
The input currents are calculated values with 100 kVA line transformer supply.
NOTE:
The mechanical dimensions of the units are given in „3.2 HVAC232/402 dimensions" on page 14.
NOTE:
For PM motor, please select the drive power rating according to motor shaft power, not rated current.
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
Table 60. Mains voltage 208 - 240 V, 50/60 Hz, 3~ series.
Rated loadability
100%
150%
continuous
overload
current I
[A]
current [A]
N
1,9
2,9
2,4
3,6
3,3
5
4,3
6,5
5,6
8,4
7,6
11,4
9
13,5
12
18
16
24
23
34,5
31
46,5
38
57
Motor shaft power
P
P
[HP]
[KW]
0,75
0,55
1
0,75
1,5
1,1
2
1,5
3
2,2
4
3
5
4
7,5
5,5
10
7,5
15
11
20
15
25
18,5
Nominal input
current
Mechanical
[A]
size
2,8
MI1
3,2
MI1
4
MI2
5,6
MI2
7,3
MI2
9,6
MI3
11,5
MI3
14,9
MI3
17,1
MI4
25,5
MI4
33
MI5
41,7
MI5
Weight
[kg]
0,55
0,55
0,70
0,70
0,70
0,99
0,99
0,99
8,68
8,68
11,07
11,07
144

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents