Honeywell HVAC232 Series Applications Manual page 79

Table of Contents

Advertisement

9.1.11 Limit Supervisions (Control panel: Menu PAR
Code
Parameter
P11.1
Output frequency supervision
function
P11.2
Output frequency supervision
limit
P11.3
Torque supervision
function
P11.4
Torque supervision
limit
P11.5
Unit Temperature Supervision
P11.6
Unit Temperature Supervision Limit
P11.7
Analogue input supervision
signal
P11.8
AI superv ON level
P11.9
AI superv OFF level
P11.10
Temperature supervision
input
P11.11
Temperature supervision function
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
P11)
Table 32. Limit Supervisions.
Min
Max
Unit
0
2
0,00
P3.2
Hz
0
2
0,0
300,0
%
0
2
–10
100
°C
0
Varies
0,00
100,0
%
0,00
100,00
%
1
7
0
2
Default
ID
Note
0
315
0 = Not used
1 = Low limit
2 = High limit
0,00
316
0
348
0 = Not used
1 = Low limit
2 = High limit
0,0
349
0
354
40
355
0
356
0 = AI1
1 = AI2
2 = AIE1
80,00
357
40,00
358
1
1431
Binary-coded selection of signals to use
for temperature supervision
B0 = Temperature input 1
B1 = Temperature input 2
B2 = Temperature input 3
NOTE! Hidden until an option board
is connected.
2
1432
As parameter 11.1, hidden until an option
board is connected.
79

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents