Code
Parameter
P2.3
Sensor 3 type
Other information
V3.1
MWh counter
V3.2
Power on days
V3.3
Power on hours
V3.4
Run counter: Days
V3.5
Run counter: Hours
V3.6
Fault counter
V3.7
Panel parameter
set status monitor
P4.2
Restore factory defaults
P4.3
Password
P4.4
Time for panel and
lcd backlight active
P4.5
Save parameter set to panel
P4.6
Restore parameter set from panel
F5.x
Active Fault menu
F6.x
Fault History menu
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
Table 39. System parameters.
Min
Max
Default
0
6
0
14074
0
1
0
0000
9999
0000
0
99
5
0
1
0
0
1
0
ID
Note
0 = No Sensor
1 = PT100
2 = PT1000
3 = Ni1000
4 = KTY84
5 = 2 × PT100
6 = 3 × PT100
827
Million Watt Hour
828
829
840
841
842
Hidden when connect with PC
831
1 = Restores factory defaults for all parameters
832
833
0 = OFF
1...60 = 1...60 min
>=60 = Always ON
Hidden when connect with PC
Hidden when connect with PC