Honeywell HVAC232 Series Applications Manual page 58

Table of Contents

Advertisement

Code
Parameter
P14.4 Feedback source selection
P14.5 Feedback value min
P14.6 Feedback value max
P14.11 Sleep min frequency
P14.12 Sleep delay
P14.13 Wake up level
P14.14 Sleep setpoint boost
P14.15 Setpoint boost time
P16.2 Parameter conceal
P18.1 Fire mode password
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
Table 21. Quick setup parameters.
Min
Max
Unit
0
Varies
0,0
50,0
%
10,0
300,0
%
0,00
P3.2
Hz
0
3600
s
0,0
100,0
%
0,0
50,0
%
0
60
s
0
1
0
9999
Default
ID
0 = AI1
1
334
1 = AI2
2 = ProcessDataIn1(0-100%)
3 = ProcessDataIn2(0-100%)
4 = ProcessDataIn3(0-100%)
5 = ProcessDataIn4(0-100%)
6 = AI2-AI1
7 = AIE1
8 = Temperature input 1
9 = Temperature input 2
10 = Temperature input 3
0,0
336
Value at minimum signal
100,0
337
Value at maximum signal
25,00
1016
Threshold for enter sleep
30
1017
Delay for enter sleep
90,0
1018
Threshold for exit sleep
10,0
1071
Referred to setpoint
10
1072
Boost time after P14.12
1
115
Hides all parameters not in quick start
0 = All parameters visible
1 = Only quick setup parameter group
visible
0
1599
1234 = Test mode
1001 = Enable
1515 = Disable
Note
58

Hide quick links: