9.1.1
Motor settings (Control panel: Menu PAR -> P1)
Code
Parameter
P1.1 Motor nominal voltage
P1.2 Motor nominal frequency
P1.3 Motor nominal speed
P1.4 Motor nominal current
P1.5 Motor cos φ (Power Factor)
P1.6 Motor type
P1.7 Current limit
P1.8 Motor control mode
P1.9 U / f ratio
P1.10 Field weakening point
P1.11 Field weakening point
voltage
P1.12 U / f mid point frequency
P1.13 U / f mid point voltage
P1.14 Zero freq voltage
P1.15 Torque Boost
P1.16 Switching frequency
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
Table 22. Motor settings
Min
Max
Unit
180
480
V
30,00
320,00
Hz
30
20000
rpm
0,2 × I
2,0 × I
A
Nunit
Nunit
0,30
1,00
0
1
0,2 × I
2,0 × I
A
Nunit
Nunit
0
1
0
2
8,00
320,00
Hz
10,00
200,00
%
0,00
P1.10
Hz
0,00
P1.11
%
0,00
40,00
%
0
1
1,5
16,0
kHz
Default
ID
Note
Varies
110
50,00/60,00
111
1440/1720
112
I
113
Nunit
0,85
120
0
650
0 = Induction
1 = Permanent magnet
1,5 × I
107
Nunit
0
600
0 = Frequency control
1 = Open loop speed control
0 = Linear
0
108
1 = Square
2 = Programmable
50,00/60,00
602
100,00
603
50,00/60,00
604
100,00
605
Varies
606
0
109
0 = Disabled
1 = Enabled
4,0/2,0
601
61