Capacitor recharge
After a longer storage time the capacitors need to be recharge in order to
avoid capacitor damage. Possible high leakage current through the capac-
itors must be limited. The best way to achieve this is to use a DC-power
supply with adjustable current limit.
1. Set the current limit to 300...800 mA according to the size of the drive.
2. Then connect the DC-power supply to the input phase L1 and L2.
3. Then set the DC-voltage to the nominal DC- voltage level of the
(1.35 × Un AC) and supply the converter for at least 1h.If DC-voltage
is not available and the unit has been stored much longer than 12
months de-energized, consult the factory before connecting power.
2.3

Warranty

Only manufacturing defects are covered by the warranty. The manufacturer
assumes no responsibility for damages caused during or resulting from
transport, receipt of the delivery, installation, commissioning or use.
The manufacturer shall in no event and under no circumstances be
held responsible for damages and failures resulting from misuse, wrong
installation, unacceptable ambient temperature, dust, corrosive substances
or operation outside the rated specifications. Neither can the manufacturer
be held responsible for consequential damages.
Variable frequency drive devices (VFD) and accessories: new products for
thirty-six (30) months from the date of production.
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
3

INSTALLATION

3.1

Mechanical installation

There are two possible ways to mount HVAC232/402 in the wall. For
MI1-MI3, either screw or DIN-rail mounting; For MI4-MI5, screw or flange
mounting.