9.1.15 Motor Pre-heat (Control panel: Menu PAR
Code
Parameter
P15.1
PreHeat function
P15.2
PreHeat current
P15.3
Heatsink temperature limit
P15.4** External temperature
selection
P15.5** External temperature limit
*
value 4 only if expansion OPTB2 is installed
** visible only if expansion OPTB2 is installed
*** unit and values depends on P16.3 Temperature unit
Application manual HVAC232/402 | Document 27-652 | Issue ENG06 | 2019-08-07
P15)
Table 36. Motor Pre-heat.
Min
Max
Unit
0
3-4 *
0
50%
A
motor
nominal
current
-10
80
°C
0
7
-50.0***
200.0***
°C***
Default
ID
Note
0 = not used
0
1225
1 = always in stop state
2 = controlled by digital input
3 = heatsink temperature limit
4 = external temperature limit
0
1227
Motor pre heat current
40
1620
Heatsink temperature to stop pre heat
1
1621
Selection of external temperature
0 = None of the temperature inputs are selected
1 = Temperature input 1 selected
2 = Temperature input 2 selected
3 = Temperature input 1 and 2 selected
4 = Temperature input 3 selected
5 = Temperature input 1 and 3 selected
6 = Temperature input 2 and 3 selected
7 = Temperature input 1, 2 and 3 selected
30.0
1622
External temperature to stop pre heat