Autorestart Parameters (Control Panel: Menu Par -> P10 ) - Honeywell SmartVFD COMPACT User Manual

Hvfdcd1b0003 series; hvfdcd1b0005 series; hvfdcd1b0007 series; hvfdcd1b0010 series; hvfdcd1b0015 series; hvfdcd1b0020 series; hvfdcd1b0030 series; hvfdcd3c0005 series; hvfdcd3c0007 series; hvfdcd3c0010 series; hvfdcd3c0015 series; hvfdcd3c0020
Hide thumbs Also See for SmartVFD COMPACT:
Table of Contents

Advertisement

Honeywell
9.10 AUTORESTART PARAMETERS (CONTROL PANEL: MENU PAR ->
P10 )
Code Parameter
P10.1 Wait time
P10.2 Trial time
P10.3 Start function
P10.4 Automatic restart
Table 9.10: Autorestart parameters
NOTE! These parameters are shown, when P13.1 = 0.
62-0312—02
Parameters
Min
Max
Unit
Default
0.10
10.00 s
0.50
0.00
60.00 s
30.00
0
2
0
0
1
0
ID
Note
Delay before automatic
717
restart after a fault has dis-
appeared
Defines the time before the
frequency converter tries to
718
automatically restart the
motor after the fault has dis-
appeared
0 = Ramp
719
1 = Flying start
2 = According to P4.2
0 = Disabled
731
1 = Enabled
9
50