Sine Filter - Lenze i550 Series Project Planning Manual

Cabinet 0.25...132 kw
Hide thumbs Also See for i550 Series:
Table of Contents

Advertisement

Comparison of integrated and external RFI filters
RFI filters
Integrated in the inverter
Use
In standard applications.
Optimisation
Easy use.
Reduces noise emissions
Cable-guided and radiated
The adapted assignment of these accessories and the technical data are provi-
ded with the devices.

Sine filter

A sinusoidal filter in the motor cable limits the rate of voltage rise and the capacitive charge/
discharge currents between the conductors that occur during inverter operation.
Only use a sinusoidal filter with standard asynchronous motors 0 to 550 V.
Operation only with V/f or square-law V/f characteristic control.
Set the switching frequency permanently to the specified value.
Limit the output frequency of the inverter to the given value.
The adapted assignment of these accessories and the technical data are provi-
ded with the devices.
Power supply units
For the external supply of the control electronics of the inverter.
The parameterisation and diagnostics can be executed when the mains input at the inverter is
deenergised.
Order code
Rated voltage
Rated mains current
Input voltage
Output voltage
Rated output current
Low Leakage
In mobile systems.
For low leakage current.
Cable-guided
EZV1200-000
EZV2400-000
V
230
A
0.8
1.2
V
AC 85 - 264
DC 90 ...350
V
A
5.0
10.0
Filter types
External
Short Distance
With short cable length.
For low leakage current.
Cable-guided
EZV4800-000
EZV1200-001
2.3
0.3
DC 22.5 - 28.5
20.0
5.0
Accessories
Power supply units
Long Distance
At switching frequencies
4 kHz and 8 kHz.
For long motor cable.
Cable-guided
EZV2400-001
EZV4800-001
400
0.6
1.0
AC 320 ... 575
DC 450 ...800
10.0
20.0
247

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents