Emc-Compliant Installation - Lenze i550 Series Project Planning Manual

Cabinet 0.25...132 kw
Hide thumbs Also See for i550 Series:
Table of Contents

Advertisement

EMC-compliant installation

Structure of a CE-typical drive system
The drive system (frequency inverter and drive) corresponds to 2014/30/EU: EMC Directive if
it is installed according to the specifications of the CE-typical drive system.
The structure in the control cabinet must support the EMC-compliant installation with shiel-
ded cables.
Please use highly conductive shield connections.
Connect the housing with shielding effect to the grounded mounting plate with a surface
as large as possible, e. g. of inverters and RFI filters.
Use central earthing points.
Matching accessories makes effective shielding easier.
Shield sheets
Shield clips/shield clamps
Metallic cable ties
Mains connection, DC supply
Inverters, mains chokes, or mains filters may only be connected to the mains via unshiel-
ded single cores or unshielded cables.
When a line filter is used, shield the cable between mains filter or RFI filter and inverter if
its length exceeds 300 mm. Unshielded cores must be twisted.
In DC-bus operation or DC supply, use shielded cables.
Only certain inverters are provided with this connection facility.
-
Rated mains voltage
V
400
480
Information on project planning
Control cabinet structure
EMC-compliant installation
DC voltage range
DC 450 V - 0 % ... 750 V + 0 %
41

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents