Fusing data
Fusing data
Inverter
Cable installation in compliance
with
without mains choke
Circuit breaker
Characteristics
Max. rated current
Fuse
Characteristics
Max. rated current
with mains choke
Circuit breaker
Characteristics
Max. rated current
Fuse
Characteristics
Max. rated current
Earth-leakage circuit breaker
3-phase mains connection
Fusing data
Inverter
Cable installation in compliance
with
without mains choke
Circuit breaker
Characteristics
Max. rated current
Fuse
Characteristics
Max. rated current
with mains choke
Circuit breaker
Characteristics
Max. rated current
Fuse
Characteristics
Max. rated current
Earth-leakage circuit breaker
3-phase mains connection
i550-C0.25/230-2
A
10
A
10
A
10
A
10
i550-C1.1/230-2
A
25
A
25
A
25
A
25
3-phase mains connection 230/240 V
i550-C0.37/230-2
i550-C0.55/230-2
EN 60204-1
B
10
16
gG/gL or gRL
10
16
B
10
16
gG/gL or gRL
10
16
≥ 30 mA, type B
i550-C1.5/230-2
i550-C2.2/230-2
EN 60204-1
B
25
25
gG/gL or gRL
25
25
B
25
25
gG/gL or gRL
25
25
≥ 30 mA, type B
Technical data
Fusing data
i550-C0.75/230-2
16
16
16
16
i550-C4.0/230-3
32
32
32
32
≥ 300 mA, type B
103