Motor Connection - Lenze i550 Series Project Planning Manual

Cabinet 0.25...132 kw
Hide thumbs Also See for i550 Series:
Table of Contents

Advertisement

Motor connection

Switching in the motor cable
Switching on the motor side of the inverter is permissible:
For safety shutdown (emergency stop).
In case several motors are driven by one inverter (only in V/f operating mode).
Please note the following:
The switching elements on the motor side must be dimensioned for with the
maximum occurring load.
Motor cable lengths
The rated data for the motor cable length must be observed.
Keep the motor cable as short as possible as this has a positive effect on the drive behav-
iour and the EMC.
Several motors connected to an inverter form a group drive.
In case of group drives, the resulting motor cable length l
l
[m] = (l
+ l
+ l
... l
) ∙ √i
res
1
2
3
i
l
Resulting length of the motor cables
res
l
Length of the single motor cable
x
i
Number of the single motor cables
Shielding
A good shield connection and short cable lengths reduce possible interferences caused by
problems with the EMC.
Example for preparing the EMC-compliant wiring or the motor cable
Fig. 10: Shield connection
Braid
large surface contacting of the braid
Information on electrical installation
is relevant:
res
l
Heat-shrinkable tube
l
maximally 500 mm
Motor connection
57