Motor connection
Switching in the motor cable
Switching on the motor side of the inverter is permissible:
For safety shutdown (emergency stop).
In case several motors are driven by one inverter (only in V/f operating mode).
Please note the following:
The switching elements on the motor side must be dimensioned for with the
maximum occurring load.
Motor cable lengths
The rated data for the motor cable length must be observed.
•
Keep the motor cable as short as possible as this has a positive effect on the drive behav-
•
iour and the EMC.
Several motors connected to an inverter form a group drive.
•
In case of group drives, the resulting motor cable length l
l
[m] = (l
+ l
+ l
... l
) ∙ √i
res
1
2
3
i
l
Resulting length of the motor cables
res
l
Length of the single motor cable
x
i
Number of the single motor cables
Shielding
A good shield connection and short cable lengths reduce possible interferences caused by
problems with the EMC.
Example for preparing the EMC-compliant wiring or the motor cable
Fig. 10: Shield connection
①
Braid
②
large surface contacting of the braid
Information on electrical installation
is relevant:
res
l
①
②
③
Heat-shrinkable tube
l
maximally 500 mm
③
Motor connection
57