... 8 Commissioning

Basic Setup

The device can be factory parameterized to customer specifications upon request. If no customer information is available, the device
is delivered with factory settings.
Settings for the most common parameters are summarized in the 'Easy Set-up' menu.
This menu is the quickest way to perform the initial configuration of the device.
For information on navigating through the transmitter menu, see Menu navigation on page 72.
For a detailed description of all menus / parameters see Parameter descriptions on page 95.

Menu: Easy Set-up

Menu / parameter
Easy Set-up
Language
Unit Massflow Qm
Qm Max
Unit Volumeflow Qv
Qv Max
Density
Density Max
Density Min
Unit Temperature
Unit Mass Totalizer
Unit Vol. Totalizer
Curr.Out 31 / 32 / Uco
Curr.Out V1 / V2
Curr.Out V3 / V4
Dig.Out 41 / 42 Mode
Description
Selection of menu language.
Selection of the unit for mass flow rate (for example for the Q
process value).
See Table 2: Units for mass flow on page 78.
Sets the upper range value for the mass flow for forward and reverse flow. The value is also used to calculate the
corresponding percentage value.
Selection of the unit for volume flow rate (for example for the Q
process value).
See Table 1: Units for the volume flow rate on page 78.
Setting of the upper measuring range value 1 for the volume flow for feed flow and reverse flow. The value is also used to
calculate the corresponding percentage value.
Selection of the unit for the density (e.g. for the associated parameters and the corresponding process values).
See Table 3: Density units on page 78.
Sets the maximum / minimum density to be measured. This value is used to calculate the percentage density value. These
parameters are only available if the density output 'Density [unit]' was selected when configuring the power and digital
outputs.
Selection of unit for temperature (e.g. for the associated parameters and the corresponding process values).
See Table 4: Temperature units on page 78.
Selection of the unit for the mass counters and the pulse outputs.
See Table 6: Units for the mass totalizer on page 79.
Selection of the unit for the volume totalizers and the pulse outputs.
See Table 7: Units for the volume totalizer on page 79.
Selection of the process value issued via the current output.
The current outputs V1 / V2 and V3 / V4 are only available if the corresponding plug-in cards are present!
Available process variables on page 80
Selection of the operating mode for the digital output 41 / 42.
Off: Digital output 41 / 42 deactivated.
Logic: Digital output 41 / 42 as a binary output (e.g. as an alarm output).
Pulse: Digital output 41 / 42 as a pulse output. In pulse mode, pulses per unit are output (e.g. 1 pulse per m
Frequency: Digital output 41 / 42 as a frequency output. In frequency mode, a frequency is issued that is proportional to
the flow rate. The maximum frequency can be configured in accordance with the upper range value.
Max / Q
MaxDN parameters and for the corresponding
m
m
Max / Q
MaxDN parameters and for the corresponding
v
v
3
).