CoriolisMaster FCB400, FCH400 CORIOLIS MASS FLOWMETER | OI/FCB400/FCH400-EN REV. E
Step 2:
Entry of the basic settings for the matrix in the menu '... /
...Variable Matrix / ...Configuration'.
Parameter
Description
Number Matrices
Selection of number of matrices.
Number Temp.
Entry of the number of temperature values for the
matrix calculation.
Number Conc.
Entry of the number of the concentration values
for the matrix calculation.
Enter Conc. in %
Selection of type of the concentration calculation.
Yes: Calculation of concentration in %
No: Calculation of concentration in a selected
unit
Qm / Qv Conc. Switch
Selection of whether the volume concentration or
mass concentration is calculated.
Step 3:
Entry of the matrices data in the menu '... / ...Variable Matrix'.
Parameter
Description
Matrix 1 Unit
Entry of the temperature, concentration and
density values to calculate the concentration in
Matrix 2 Unit
the selected unit.
Matrix 1 Percent
Entry of the temperature, concentration and
density values to calculate the concentration in %.
Matrix 2 Percent
Once the data has been entered, select 'Calculate matrix' from
the menu to calculate the matrix. Missing values are interpolated
or extrapolated.
Step 4:
Saving the matrices in the menu '... / ...Variable Matrix' using the
menu item 'Enter Matrix Finish'.
This completes the process to enter the matrices.
Change from two to one column
127