CoriolisMaster FCB400, FCH400 CORIOLIS MASS FLOWMETER | OI/FCB400/FCH400-EN REV. E
... 7 Electrical connections
... Pin assignment
Flowmeter sensor
A Signal cable from the sensor
1 Terminal for potential equalization
Figure 51: Connection to sensor in remote mount design (example)
Change from one to two columns
NOTICE
If the O-ring gasket is seated incorrectly or damaged, this
may have an adverse effect on the housing protection class.
Follow the instructions in Opening and closing the housing
on page 38 to open and close the housing safely.
Terminal
ABB signal cable
3KQZ407123U0100
GND
Blue
U
White
FE
A
Yellow
B
Orange
2 Terminals for signal cable
Observe the following points when connecting to an electrical
supply:
HELKAMA signal cable
20522
Blue (4)
white (3)
Blue (2)
white (1)
Lead the signal cable into the housing as shown.
Connect the cables in accordance with the electrical
connection. If present, connect the cable shielding to the
earthing clamp provided.
Use wire end ferrules when connecting.
From an ambient temperature of T
additionally insulate the wires with the enclosed silicone
hoses.
Close unused cable entries using suited plugs.
≥ 60 °C (≥ 140 °F)
amb.