CoriolisMaster FCB400, FCH400 CORIOLIS MASS FLOWMETER | OI/FCB400/FCH400-EN REV. E
... 9 Operation
... Parameter descriptions
Menu / parameter
Communication / ...Modbus
Address
IEEE Format
Baud Rate
Parity
Stop Bits
Response Delay
Communication / ...Profibus
Address
Ident Nr. Selector
Comm State
Baud Rate
PB Manufacturer ID
Description
Setting the Modbus® device address (1 to 127).
Selection of the byte order for the Modbus communication.
Enabled: If the IEEE format is activated, the data words are sent in the 'little endian' format with the lowest value word
first.
Disabled: If the IEEE format is deactivated, the data words are sent in the standard Modbus 'bigendian' format.
Factory setting: Enabled.
Selection of the transmission speed (baud rate) for the Modbus communication.
Factory setting: 9600 baud.
Selection of the parity for the Modbus communication.
Factory setting: Odd.
Selection of the stop bits for the Modbus communication.
Factory setting: One stop bit
Setting of the pause time in milliseconds after receiving a Modbus command. The device sends a response no earlier than
expiration of the set pause time.
Factory setting: 10 ms
Set the PROFIBUS DP® device address (1 to 126).
Display the PROFIBUS DP® identification number
0x9741: 2AI + 1TOT
0x9742: 3xAI + 1xTOT
0x3434: ABB specific
Display the PROFIBUS communication status.
Offline: No PROFIBUS® communication.
Stop: Bus active, device not active.
Clear: Device is being initialized.
Operate: Cyclic communication is active.
Display the transmission speed (baud rate) for the PROFIBUS® communication.
The baud rate is automatically detected and does not need to be configured manually.
Display the PROFIBUS DP® manufacturer ID
26: ABB