CoriolisMaster FCB400, FCH400 CORIOLIS MASS FLOWMETER | OI/FCB400/FCH400-EN REV. E
Limits and rules when using ABB fieldbus accessories
Figure 53: Bus cable length depends on the transmission rate
Pro PROFIBUS Line
(Line = Starts at DP Master and goes to last DP/PA Slave)
Approximately 4 to 8 DP segments through the repeater (see
repeater data sheets)
Recommended DP transfer rate 500 to 1500 kBit/s
The slowest DP node determines the transfer rate of the DP
line
Number of PROFIBUS DP and PA nodes ≤ 126 (addresses
0 to 125)
Per PROFIBUS DP segment
Number of DP nodes ≤ 32
(Node = Devices with / without PROFIBUS address)
Bus termination required at the beginning and end of each
DP segment!
Trunk cable length (L
) see diagram (length dependent on
T
transfer rate)
Cable length of at least 1 m between two DP nodes at
≥ 1500 kBit/s!
Spur cable length (L
), at ≤ 1500 kBit/s: LS ≤ 0.25 m,
S
at > 1500 kBit/s: LS = 0.00 m!
At 1500 kBit/s and ABB DP cable type A:
Sum of all spur cable lengths (L
length (L
) > 6.60 m, total length = L
T
maximum 22 DP nodes (= 6.60 m / (0.25 m + 0.05 m
spare))
) ≤ 6.60 m, trunk cable
S
+ (Σ L
) ≤ 200 m,
T
S