Connecting The Digital Inputs/Outputs - Siemens SIMOTION D410 Manual

Hide thumbs Also See for SIMOTION D410:
Table of Contents

Advertisement

5.7

Connecting the digital inputs/outputs

Connecting cables for digital inputs/outputs
Use flexible cables with a cross-section of at least 0.25 mm² when you wire the digital
inputs/outputs.
If you wire two cables per connection, use cables with a cross-section of 0.25 mm² each and
a wire-end sleeve. Use wire-end sleeves without insulating collars according to DIN 46228,
Form A long version.
Note
Shielded cables are required when connecting measuring inputs or external zero marks for
optimal noise immunity.
Tools required
3.5-mm screwdriver or power screwdriver
Wiring digital inputs/outputs
1. Strip the cable ends 6 mm.
2. Put on the wire-end sleeve if applicable.
3. Wire the interface digital inputs for the connection of sensors.
4. Wire the interface digital outputs for the connection of actuators.
5. Insert the cable into the corresponding spring-loaded terminal.
D410
Manual, 03/2007 Edition
5.7 Connecting the digital inputs/outputs
Connecting
53

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simotion d410 dpSimotion d410 dn