5.7
Connecting the digital inputs/outputs
Connecting cables for digital inputs/outputs
Use flexible cables with a cross-section of at least 0.25 mm² when you wire the digital
inputs/outputs.
If you wire two cables per connection, use cables with a cross-section of 0.25 mm² each and
a wire-end sleeve. Use wire-end sleeves without insulating collars according to DIN 46228,
Form A long version.
Note
Shielded cables are required when connecting measuring inputs or external zero marks for
optimal noise immunity.
Tools required
3.5-mm screwdriver or power screwdriver
Wiring digital inputs/outputs
1. Strip the cable ends 6 mm.
2. Put on the wire-end sleeve if applicable.
3. Wire the interface digital inputs for the connection of sensors.
4. Wire the interface digital outputs for the connection of actuators.
5. Insert the cable into the corresponding spring-loaded terminal.
D410
Manual, 03/2007 Edition
5.7 Connecting the digital inputs/outputs
Connecting
53