Technical data

6.4 Shipping and storage conditions

6.4
Shipping and storage conditions
The control exceeds the requirements according to DIN EN 60068-2 with regard to shipping
and storage conditions. The following information applies to modules shipped and stored in
the original packaging.
Table 6-7
Type of condition
Free fall, checked according to
DIN EN60721-3-2, Class 2M2
Temperature
Air pressure
Relative humidity
6.5

Mechanical and climatic ambient conditions

Conditions of use
SIMOTION D410 is designed for use in stationary, weather-protected locations. The
conditions of use exceed the requirements of the environmental test according to
DIN IEC 60068-2-2.
SIMOTION D410 meets the conditions of use, Class 3C3, according to DIN EN 60721-3-3
(operating locations with high traffic densities and in the immediate vicinity of industrial
equipment with chemical emissions).
Use prohibition
Without additional measures, SIMOTION D410 may not be used in
• Locations with a high percentage of ionizing radiation
• Locations with extreme operating conditions, e.g.,
• In systems, which require special monitoring, e.g.,
An additional measure for using SIMOTION D410 can, for example, be installation in
cabinets.
64
Shipping and storage conditions
– Dust accumulation
– corrosive vapors or gases
– Elevator installations
– Electrical systems in particularly hazardous rooms
Permissible range
≤ 1 m
Shipping: -40 °C to +70 °C
Storage: -25 °C to +55 °C
from 1060 to 700 hPa (equals a height of 3000 m)
5% to 95%, without condensation