3.9 Measuring sockets

3.9
Measuring sockets
Interface features
The T0 - T2 measuring sockets are used to output analog signals Any interconnectable
signal can be output to any measuring socket on the control unit.
Note
The measuring sockets are suited for multiple-spring wire connectors with a diameter of
2 mm.
Interface assignments
Table 3-17
Interface assignments T0, T1 and T2
View
3.10

Power Module Interface

SIMOTION D410 can be connected to a blocksize power module via the power module
interface.
Note
SIMOTION D410 can only be connected to a blocksize power module via the power module
interface. You must connect a chassis power module via the DRIVE-CLiQ interface (see
chapter "Connecting DRIVE-CLiQ Components").
See also
SIMOTION D410 mounted on the power module (Page 43)
42
Pin
Designation
T0
Measuring socket 0
T1
Measuring socket 1
D2
Measuring socket 2
G
Ground
Technical details
Voltage: 0 V to 5 V
Resolution: 8-bit
Load current: max. 3 mA
sustained short-circuit proof
Reference potential is G terminal