Resetting To Default Values - Samson TROVIS 5573 Mounting And Operating Instructions

Automation system trovis 5500 heating and district heating controller
Table of Contents

Advertisement

Storage tank sensor SF1
Storage tank sensor SF2
Storage tank sensor of the solar circuit SF2
9.
Display measured value [ ].
"°C" blinks.
10. Correct measured value [q].
Read the actual temperature directly from the thermometer at the point of measurement
and enter this value as the reference temperature.
11. Confirm corrected measured value [ ].
Additional sensors are calibrated similarly.
12. Select End [q].
13. Return the rotary switch to normal switch position
2.5

Resetting to default values

All parameters set over the rotary switch as well as parameters in PA1, PA2 and PA5 parameter
levels can be reset to their default settings (WE), except for the maximum flow temperature and
the return flow temperature limits in PA1 and PA2.
1.
Turn the rotary switch to
Display: 0 0 0 0
2.
Set key number 1991 [q].
3.
Confirm key number [ ].
The controller is reset to its default settings.
Display: 0 0 0 0
(configuration and parameter level).
(information level).
Start-up
25
EB 5573 EN