Appendix; Function Block Lists - Samson TROVIS 5573 Mounting And Operating Instructions

Automation system trovis 5500 heating and district heating controller
Table of Contents

Advertisement

12

Appendix

12.1

Function block lists

CO1: Rk1· Heating circuit 1 (not system Anl 1.9)*
F Function
01 Room sensor RF1
02 Outdoor sensor
AF1
03 Return flow sensor
RüF1
04 Reserved
05 Underfloor heating
Drying of jointless
floors
06 Reserved
07 Optimization
08 Adaptation
09 Flash adaptation
10 Reserved
Comment
Function block parameters / Range of values (default)
WE
Anl
0
Not in Anl
CO1 -> F01 - 1: Temperature display and input FG1 for
1.5, 1.6,
Type 5244/5257-5 Room Panel active
3.x
TROVIS 5570 Room Panel:
CO1 -> F01 - 1 and CO7 -> F03 - 1
0
1.5, 1.6 CO1 -> F02 - 1: Weather-compensated control active
1
Not in Anl
1.5, 1.6
0
1.2
CO1 -> F03 - 1: Sensor and limiting function active
Function block parameter:
1
Not in Anl
KP (limiting factor) / 0.1 to 10.0 (1.0)
1.2
0
Not in Anl
CO1 -> F05 - 1: Limitation of the adjustment ranges
1.5, 1.6,
Function block parameters:
3.x
Start temperature / 20 to 60 °C (25 °C)
Temperature rise per day / 1.0 to 10.0 °C (5.0 °C)
Maximum temperature / 25.0 to 60.0 °C (45.0 °C)
Maintaining time of max. temp. / 0 to 10 days (4 days)
Temperature reduction per day / 0.0 to 10.0 °C (0.0 °C)
SToP,
0
Not in Anl
CO1 -> F07 - 1: Only with
1.5, 1.6,
3.x
0
Not in Anl
CO1 -> F08 - 1: Only with
1.5, 1.6,
3.x
0
Not in Anl
CO1 -> F09 - 1 Only with CO1 -> F01 - 1
1.5, 1.6,
Function block parameters:
3.x
Cycle time / 0 or 1 to 100 min (20 min)
KP (gain) / 0.0 to 25.0 (0.0)
n
nn
nnn
STArT,
STArT,
Appendix
STArT
• CO1 -> F01 - 1
• CO1 -> F02 - 1
• CO1 -> F01 - 1
• CO1 -> F02 - 1
• CO1 -> F11 - 0
EB 5573 EN
93