Calibrating Sensors - Samson TROVIS 5573 Mounting And Operating Instructions

Automation system trovis 5500 heating and district heating controller
Table of Contents

Advertisement

Start-up
2.4

Calibrating sensors

The controller is designed for the connection of Pt 1000 sensors.
The resistance values of the Pt 1000 sensors can be found on page 112.
If the temperature values displayed at the controller differ from the actual temperatures, the
measured values of all connected sensors can be readjusted. To calibrate a sensor, the currently
displayed sensor value must be changed such that it matches the temperature (reference tem-
perature) measured directly at the point of measurement.
Sensor calibration is to be activated in CO5 via function block F20.
An incorrect sensor calibration can be deleted by setting F20 - 0.
Proceed as follows:
1.
Turn the rotary switch to
Display: 0 0 0 0
2.
Set valid key number [q].
3.
Confirm valid key number [ ].
Display: PA_
4.
Select CO5 configuration level [q].
5.
Open CO5 configuration level [ ].
6.
Select function block F20 [q].
7.
Activate editing mode for function block F20 [ ].
8.
Select appropriate sensor icon [q]:
Room sensor RF, heating circuits 1 and 2
Outdoor sensor AF1
Flow sensor VF, heating circuits 1 and 2
Flow sensor VF1, primary heat exchanger circuit
Flow sensors VF2 and VF4, DHW circuit
Solar collector sensor VF3
Return flow sensor RüF