Fixed Set Point Control - Samson TROVIS 5573 Mounting And Operating Instructions

Automation system trovis 5500 heating and district heating controller
Table of Contents

Advertisement

Functions of the heating circuit
Parameters
Flow
Point 1
temperature
Point 2
Point 3
Point 4
Reduced flow
Point 1
temperature
Point 2
Point 3
Point 4
Return flow
Points 1 to 4
temperature
Min. flow temperature
Max. flow temperature
* With CO1, 2 -> F05 - 1, the following applies: Max. flow temperature / 5 to 50 °C (50 °C)
5.2

Fixed set point control

During the times-of-use, the flow temperature can be controlled according to a fixed set point.
Outside the times-of-use, the controller regulates to a reduced flow temperature.
Set the desired rated flow temperature as Day set point , and the reduced flow temperature as
Night set point .
Functions
Outdoor sensor AF1
Parameters
Day set point
Night set point
Parameters
Min. flow temperature
Max. flow temperature
Note: A fixed set point control in heating circuit 2 can only be configured with CO2 -> F02 - 0 if
CO1 -> F02 - 0 is also configured as heating circuit 2 configured with CO2 -> F02 - 0 only uses
the measured outdoor temperature provided by heating circuit 1.
50
EB 5573 EN
WE
Parameter level / Range of values
70.0 °C
PA1, 2 / 5.0 to 130.0 °C
55.0 °C
40.0 °C
25.0 °C
60.0 °C
PA1, 2 / 5.0 to 130.0 °C
40.0 °C
20.0 °C
20.0 °C
65.0 °C
PA1, 2 / 5.0 to 90.0 °C
20.0 °C
PA1, 2 / 5.0 to 130.0 °C
90.0 °C*
PA1, 2 / 5.0 to 130.0 °C
WE
Configuration
1
CO1 -> F02 - 0
WE
Switch position / Range of values
50.0 °C
/ Min. to max. flow temperature
30.0 °C
/ Min. to max. flow temperature
WE
Parameter level / Range of values
20.0 °C
PA1, 2 / 5.0 to 130.0 °C
90.0 °C
PA1, 2 / 5.0 to 130.0 °C

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents